Steam from steam
A clean steam generator has no burner. Plant steam at 75 to 150 psig flows through a U-tube bundle submerged in feedwater on the shell side, the feedwater boils, and a separator above the bundle delivers dry steam at 30 to 60 psig to the header. The design keeps the two steams apart with a double tubesheet, holds the bundle covered with level control, and removes what the feedwater left behind with blowdown.
The parent page sizes the generator on the SIP peak. This page is about the generator as a machine: the plant steam pressure it needs, 3-A 609 culinary and USP pure steam as the two targets, and the blowdown arithmetic.
To make clean steam at 45 psig, saturation 292 F, the plant steam in the tubes must boil water at that pressure through a tube wall with a film on it. That takes 30 to 50 degrees of approach, so 100 psig plant steam at 338 F is the usual minimum and 125 to 150 psig gives a smaller bundle. A site with only 50 psig plant steam can make 15 psig clean steam, enough for barriers and low-pressure SIP but not for a 250 F sterilization at any speed. Hot oil or 350 F hot water works where there is no high-pressure steam, with a larger bundle.
Feedwater preheating pays: plant steam condensate leaving the tubes at 300 F warms feedwater from 70 F to 180 F in a small 316L exchanger and cuts the plant steam by 10 to 15 percent.
The feedwater and finish set the grade. Culinary steam under 3-A Accepted Practice 609 can contact food: potable feedwater, only boiler compounds the FDA lists as acceptable, a stainless header with a separator and a filter at the use point. A generator fed with softened, filtered water and no treatment chemicals makes 609 steam directly. Pure steam is the pharmaceutical grade: its condensate must meet the USP monograph for Water for Injection on conductivity, TOC and endotoxin, so the feed is WFI or qualified purified water, the shell side is electropolished 316L, and the separator delivers a dryness of 0.95 or better with non-condensables under 3.5 percent.
Whatever the feedwater brings in stays in the shell when the steam leaves. RO permeate at 10 microsiemens concentrates ten times in a shell blowing down at 10 percent of the steam rate, and the shell water sits at 100 microsiemens carrying ten times the permeate's chloride, hot, against 316L tubes. The blowdown rate is set from the feedwater conductivity at 10 to 20 cycles of concentration and held by a continuous blowdown valve on a conductivity controller; intermittent bottom blowdown removes what settles. The feedwater pump is sized for steam rate plus blowdown.
Level control keeps the bundle covered under a swinging load: a 3,000 lb/h SIP draw on a small shell can uncover the top tubes in a minute, superheating the steam and scaling the tube. A shell sized for the swell, a modulating feedwater valve and a low-level cutout on the plant steam are the answer.
Feeding a clean steam generator with softened water because the plant boiler uses it. Softening swaps hardness for sodium and leaves silica and chloride, so the shell water climbs to several thousand microsiemens, silica carries over, the condensate fails conductivity and the tubes pit. Clean steam takes RO or purified water; only culinary steam tolerates softened feed.
Call and talk it through with an engineer: 1-805-484-2992
These rows describe the generator we size, from capacity to the quality of steam delivered. Use them to check the match with your use, and send the steam demand and feedwater details with the quote request.
| Condition | Detail |
| Fluid | Feedwater: softened and filtered for culinary; RO or purified water for clean steam; WFI for pure steam |
| Capacity | 100 to 5,000 lb/h; SIP peaks three to five times the hold load |
| Temperatures in / out | Feedwater 60 to 200 F in; clean steam saturated at 30 to 60 psig, 274 to 308 F |
| Hold | Shell water at saturation; blowdown continuous plus intermittent |
| Utility | Plant steam at 75 to 150 psig in the tubes; hot oil or high-temperature hot water on some sites |
| Approach | Plant steam 30 to 50 degrees above clean steam saturation |
| Construction | Vertical or horizontal U-tube reboiler, double tubesheet, integral or separate separator |
| Finish / class | 316L shell side, 20 to 25 Ra electropolished for pure steam; 32 Ra for culinary; ASME stamped |
| Steam quality | Culinary to 3-A 609; clean steam tested for dryness and non-condensables; pure steam condensate to USP WFI |
| CIP / SIP | Shell side drained and flushed on schedule; passivated after any repair |
Steadily, as long as the plant steam valve can turn down to the barrier load without hunting. A generator sized for a 3,000 lb/h SIP peak may see 100 lb/h of barrier load at night, a 30 to 1 turndown that a single valve cannot hold near its seat. A second, smaller plant steam valve in split range carries the quiet hours. Level control is easy at low load and the separator has little to do, so a pressure trace that wanders at night is a valve problem when it is a problem at all.
Vertical where floor space is short and dryness matters most; horizontal where headroom is short or capacity is large. A vertical shell gives disengagement height above the water line, which is what lets the separator hold 0.95 dryness under a swinging SIP load; a horizontal shell offers more water surface for the same height and suits 3,000 lb/h and up under a low ceiling. Either needs room to pull the U-tube bundle.
Yes. It is plant steam condensate that has only passed through the tubes, and the double tubesheet is what lets you return it with confidence. A weeping joint drains to the open gap instead of mixing the two waters, so a drip on the floor is the warning rather than a conductivity excursion in the boiler. Run it through the feedwater preheater first: condensate from 150 psig steam at about 366 F warming feedwater from 70 to 180 F takes roughly 110 Btu off every pound of clean steam the generator makes, about 10 percent of the plant steam. The clean-side blowdown is a different stream and goes to drain through a cooler.
Pressure control on the plant steam valve, level control on the feedwater valve, a low-level cutout, conductivity-controlled blowdown and relief on both sides. Sites that test steam quality add the sampling condenser connections and a conductivity probe on the condensate. Say which control system the generator reports to, 4 to 20 mA or a fieldbus, and whether the site wants the low-level trip hardwired independent of the PLC; most pharmaceutical sites do. Relief set points go on the drawing.
Plant steam on slowly, shell vented of air as it heats, and the first steam to drain until condensate conductivity at the sample point is in range. Opening straight to the header pushes air and stale shell water to the users, and an autoclave or SIP cycle that was waiting takes it. On a shell that has sat full for a weekend, blow down to near the low-level point and refill with fresh feedwater before heating, because the standing water has picked up whatever the shell surface released. The same routine applies after any shutdown long enough for the shell to cool.
Level falls, the low-level cutout closes the plant steam, and clean steam stops, possibly mid-SIP or with barriers live on a filler. The protection is a break tank sized for the time it takes to restore supply: a 3,000 lb/h generator at 10 percent blowdown draws about 6.6 gpm, so a 200 gallon break tank buys 30 minutes. Give the generator a priority draw on the purified water loop ahead of the use points, and duplicate the feed pump on any line where a barrier outage means discarded product.
Sterilizer to filler: the steam seals that keep the line sterile and the scheduled process that proves it.
+ Learn More
Where the steam goes after its work: 250 F condensate to a drain that stops at 140 F, and samples at 77 F.
+ Learn More
Making plant steam fit to touch food: what 3-A 609 asks for, where separator and filter go, how it is tested.
+ Learn More